Fluorine free foam
Applications
US/European Class A Fires Wood, Grass, Coal, Tires, Hay, Cotton, Cardboard, Initial Knockdown: 0.25%
Wetting Agent: 0.25%-1.0%. Reapply as needed
Cars, Trucks, Heavy Equipment: 0.50% up to 1.0%
US Class B, European Class B/C Fires Non-Polar Solvents: Indirect Application
Gasoline, Gasoline w/10% Ethanol, Jet A, JP4/5/8, Crude Oil, Diesel, Etc. 6% using 0.1gpm/ft² for 10-20 minutes. Reapply as needed.
US Class B, European Class B/C Fires Non-Polar Solvents: Direct Application
Gasoline, Gasoline w/10% Ethanol, Jet A, JP4/5/8, Crude Oil, Diesel, Etc. 6% using 0.16gpm/ft² for 10-20 minutes. Reapply as needed.
Polar Solvents: Ethanol, Gasonline w/ 85% Ethanol, MEK, MTBE, IPA, etc. 6% using 0.3gpm/ft² for 20 minutes. Reapply as needed.
US/European Class D fires/EV fires: Recommended application is 3% or 6% using proper equipment.
Shelf Life
20 years in original sealed containers when stored at recommended temperatures.
Features
Compatible with all regular and all standard equipment, Excellent burnback protection, Rapid cooling properties, Vapor Barrier, Applicable for Training at 1%, 3%, and 6% for low, medium, and high expansion, Effective with Fresh Water and Sea Water
Physical Properties
Color: Orange
PH: 7.8
Viscosity 4/60 rpm: 1240 cps
Density: 1.000 - 1.020
Drain Time: 18:46
Certifications
• UL 162 Foam Liquid Concentrate EX28303 6%
• EN1568:3 Low Expansion Foam at 1% Fresh and Seawater
• EN1568:1 Medium Expansion Foam at 3% Fresh and Seawater
• ICAO Level B 6%
Performance
• Biodegrability: BOD28 = 83.8%
• Aquatic Toxicity OECD #201 Alga LC50 > 10mg/L
• Aquatic Toxicity OECD #202 Dapnia EC50 > 402 mg/L
• Aquatic Toxicity OECD #203 Fish LC50 > 37.5 mg/L
• Bacteria: DIN EN ISO 38412-3: 1.5 ml/l
• TOF <1PPM